Technical Definitions

Definitions taken directly from NFPA 5000 (2015 Edition) are in italics. Definitions taken from the Merriam-Webster Dictionary are underlined.

All-out evacuation strategy

An “all-out” evacuation can only be assumed if there is the ability to sound the alarm throughout all areas of the building using an “all-out” or “allcall” button at the main fire alarm panel. As most high rise buildings adopt a phased evacuation strategy, an all-out alarm would usually be activated manually by the fire department or building management

Cavity barrier or fireblocking

A material, a barrier, or construction installed in concealed spaces to prevent the extension of fire for an unspecified period of time.  In some countries the cavity barrier of fireblock may be specified for a particular fire resistance period such as 15 minutes.

Combustible material

A material that, in the form in which it is used and under the conditions anticipated, will ignite and burn; a material that does not meet the definition of non-combustible or limited-combustible.

Façade system

The assembly of framing and materials used to envelope a building.  NFPA 5000 treats a façade system as a load bearing exterior wall or nonloadbearing exterior wall

Flame spread

The propagation of flame over a surface

Flame spread index

A comparative measure, expressed as a dimensionless number, derived from visual measurements of the spread of flame versus time for a material tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials or UL 723, Standard for Test for Surface Burning Characteristics of Building Material

Fire resistance

The time, in minutes or hours, that materials or assemblies have withstood a standard fire exposure as determined by standard testing to ASTM E119 or equivalent.

Ignition

The process or means of igniting fuel; the starting of a fire

Limited combustible material

A material shall be considered a limited-combustible material where both of the following conditions are met:

  1. The material does not comply with the requirements for a noncombustible material.
  2. The material, in the form in which it is used, exhibits a potential heat value not exceeding 8141 kJ/kg (3500 Btu/lb),when tested in accordance with NFPA 259, Standard Test Method for Potential Heat of Building Materials.

And

7.1.4.2.1 The material shall have a structural base of non-combustible material with a surfacing not exceeding a thickness of 3.2 mm where the surfacing exhibits a flame spread index not greater than 50 when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials.

or

The material shall be composed of materials that in the form and thickness used, neither exhibit a flame spread index greater than 25 nor evidence of continued progressive combustion when tested in accordance with ASTM E 84 or ANSI/UL 723 and are of such composition that all surfaces that would be exposed by cutting through the material on any plane would neither exhibit a flame spread index greater than 25 nor exhibit evidence of continued progressive combustion when tested in accordance with ASTM E 84 or ANSI/UL 723.

Or

A material that is classified as A2 by the EN 13501-1 test series.

Non-combustible material

A material that complies with any one of the following shall be considered a non-combustible material:

  1. The material, in the form in which it is used, and under the conditions anticipated, will not ignite, burn, support combustion, or release flammable vapors when subjected to fire or heat.
  2. The material is reported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 °C.
  3. The material is reported as complying with the pass/fail criteria of ASTM E 136 when tested in accordance with the test method and procedure in ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 °C.

or

A material that is classified as A1 by the EN 13501-1 test series.

Perimeter fire stopping or perimeter fire barrier joint systems

A listed opening protective in the joint between the perimeter of a fire rated floor slab and the façade (exterior wall) of a building.

Smoke developed index

A comparative measure, expressed as a dimensionless number, derived from measurements of smoke obscuration versus time for a material tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials or UL723, Standard for Test for Surface Burning Characteristics of Building Materials. 

Spandrel

A spandrel beam is the edge beam on the perimeter of a structure, spanning between adjacent perimeter columns. In this FRA tool, a spandrel is used to define the area of opaque façade system covering this structural beam and floor slab.

Stay-put evacuation strategy

A stay put (defend in place) evacuation strategy assumes that building occupants not affected by a fire directly in their apartment, remain in their apartment. Only the apartment affected by a fire/smoke would be in alarm and only these occupants would be expected to evacuate. If fire/smoke spreads then the smoke detector and fire alarm in further smoke affected units would be expected to automatically activate but there is no ability to simultaneously raise the alarm in all areas of the building. The fire alarm system is not networked to a main fire alarm control panel at the entry or other designated area in the building.

Substrate

The structural wall, frame and/or floor that the façade system is fixed to

Structural Insulated Panel

For the purposes of this guide a structural insulated panel (SIP) is two layers of metal (often steel) with a foam or mineral wool insulation layer between.  These are also commonly called insulated metal panels or sandwich panels

Thermal barrier

A material, product, or assembly that prevents or delays ignition of an unexposed surface by limiting the temperature rise and by acting as a flame exposure barrier.  NFPA 5000 and the International Building Code (IBC) would require this between a combustible façade system that achieves compliance with NFPA 285 and the interior of the building.